800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
65
DKRX24-3-T, DKRX(B)24-3-T N4(H)
NEMA 2/NEMA 4 Actuators, On/Off, Floating Point
W236_11
On/Off
1
24 VAC Tr ansformer (AC Only)
Blk (1) Common
Red (2) + Hot
Wht (3) +
Line
Volts
5
GK
Y input
1
Pnk (4)
W236_13
On/Off control
W399_10
Floating Point control
Wiring Diagrams
1
Provide overload protection and disconnect as required.
2
CAUTION Equipment Damage!
Actuators may be connected in parallel if not mechanically mounted
to the same shaft. Power consumption and input impedance must be
observed.
4
Position feedback cannot be used with Triac sink controller.
The actuator internal common reference is not compatible.
5
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
8
Contact closures A & B also can be triacs.
A & B should both be closed for triac source and open for triac sink.
9
For triac sink the common connection from the actuator
must be connected to the hot connection of the controller.
Meets UL requirements without the need of an electrical ground
connection.
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed
electrician or other individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow all electrical safety
precautions when exposed to live electrical components could result in death or
serious injury.
Electrical Installation
Wiring diagram
Y
U
1 32 5
– +
T
~
Cable colors:
1 = black
2 = red
3 = white
5 = orange
Cable lengths
Y
U
1
3
2
5
T
~
A
C
L
1
L
2
L
to
t
A = Actuator
C = Control unit
L
1
= Belimo connecting cable, 1 m (4 x 0.75 mm
2
)
L
2
= Customer cable
L
tot
= Maximum cable length
Cross section
L
2
T
/
~
Max. cable length
L
tot
= L
1
+ L
2
Example for DC
AC DC
0.75 mm
2
<30 m <5 m1 m (L
1
) + 4 m (L
2
)
1.00 mm
2
<40 m <8 m1 m (L
1
) + 7 m (L
2
)
1.50 mm
2
<70 m <12 m1 m (L
1
) + 11 m (L
2
)
2.50 mm
2
<100 m <20 m1 m (L
1
) + 19 m (L
2
)
LN
Y
U
T
1
3
2
5
A
C
AC 24 V
AC 230 V
L
1
A = Actuator
C = Control unit
L
1
= Belimo connecting cable, 1 m (4 x 0.75 mm
2
)
Note
Connect via safety isolation transformer.
Parallel connection of other actuators possible.
Note performance data for supply.
!
DC 0 ... 10 V
DC 2 ... 10 V
Note
When several actuators are connected in parallel,
the maximum cable length must be divided by the
number of actuators.
Note
There are no special restrictions on installation if
the supply and data cable are routed separately.
...3
O50904 - 02/12 - Subject to change. © Belimo Aircontrols (USA), Inc.