800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
11
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
EFB24-SR(-S)
3 4
Blk (1) Common
Red (2) + Hot
Wht (3) Y Input,
2 to 10
24 VAC Transformer
6
Control Signal
(+)
VDC/mA
(–)
Feedback Signal
(+)
2 to 10 VDC
(–)
Ω
500 Ω
Line
Volts
LF24-SR(-S) US
CW CCW
3 4
NFB24-SR(-S)
AF24-SR US
Blk (1) Common
Red (2) + Hot
Wht (3) Y Input,
2 to 10V
24 VAC Transformer
8
Control Signal
(+)
VDC/mA
(–)
Ω
500 Ω
Line
Volts
AFA24-SR US
TF24-SR(-S) US
Actuators: EFB24-SR(-S) EFX24-SR(-S) AFB24-SR(-S) AFX24-SR(-S) AF24-SR US AFA24-SR US
NFB24-SR(-S) NFX24-SR(-S) LF24-SR(-S) US TF24-SR(-S) US
Equipment damage!
Up to four actuators may be connected in parallel if not
mechanically linked. Power consumption and input
impedance must be observed.
4
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Hazard Identification
Meets cULus requirements without the need of an
electrical ground connection.
A 500 Ω resistor converts the 4 to 20 mA control
signal to 2 to 10 VDC.
APPLICATION NOTES
Actuators with plenum rated cable do not have
numbers on wires; use color codes instead.
Actuators with appliance cables are numbered.
3
Actuators may also be powered by 24 VDC.
5
Only connect common to neg. (–) leg of control circuits.
6
INSTALLATION NOTES
8
7
The AFA24-SR US and TF24-SR(-S) US are supplied
without position feedback.
7
7
5
(5) U Output,
2 to 10V
6
5
W233_A_11
NFX24-SR(-S)
†
EFX24-SR(-S)
AFB24-SR(-S)
AFX24-SR(-S)
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.
Actuator ColorWire Number
5 Org
5 Org
5 Org
5 Org
5 Wht
†
NFB24-SR(-S) 5 Org
NFX24-SR(-S) 5 Org
LF24-SR US 5 Grn
LF24-SR-S US 5 Wht
AF24-SR US
EFB24-SR(-S)
EFX24-SR(-S)
AFB24-SR(-S)
AFX24-SR(-S)
Wiring for Damper Actuators and Control Valves
Proportional, Spring Return, 24V
Refer to page 26 for auxiliary switch (-S models) wiring.